Welcome to DANBIT IT Professionals
B2B – Business to business only
Multi input Data logger for up to 70000 loggings
10/100 Mbit Ethernet
Password-protected, web-based configuration and control
4 digital inputs, compatible with S0 pulse interface
6 analog inputs with 0/10V and 0/20mA
MODBUS RTU interface for up to 24 sensors (registers)
Up to 24 channels for monitoring
Up to 24 independent alarms
SNMP v.2 support - SNMP Trap - alarm notifications
HTTP and SNMP port change - HTTP API commands
Periodic HTTP posting of XML/JSON status files to client-server systems
MODBUS TCP/IP support
Dynamic DNS with DynDNS, No-IP and DNS-O-Matic support
NTP protocol support
Supply voltage: 10 to 28V DC
Dimensioner | 145 x 90 x 40 |
---|---|
Driftstemperatur | -20° - +55°C |
Hukommelse | Internal FLASH memory Settings segment endurance: 100 000 cycles (Every setting change is a memory cycle). Data logger segment endurance: 100 000 cycles of 70000 records. Update segment endurance: 100 000 cycles (updates). |
Indgang | Isolation: Isolated (1000VDC) Mode: OPEN/CLOSED (“Dry contact”) or COUNTER (S0-pulse interface outputs) Maximum input voltage: +5.5VDC Sampling rate: 1mS Digital filtering time interval: 5 to 60000mS Isolation: Isolated (1000VDC) Type: Single ended Resolution: 10 bits Mode: Voltage or current loop Input Range: 0/10V or 0/20mA Accuracy: ±1% Sampling Rate: 600mS per channel (averaged value of 100 samples) Input Impedance: 1 mega-ohm (min.) |
Luftfugtighed | 10 to 80% (non-condensing) |
Strømforbrug | 220 mA @ 12 VDC (without RS-485 powering) |
Strømforsyning | 10 til 32V DC |
Weight | 200g |
TcW260 is an energy monitoring module with an Ethernet interface and data logger functionality. All its inputs are galvanically isolated from the power supply.
The module has 4 digital inputs, S0 compatible.
The digital inputs can work in ON / OFF or counter mode. There are also 6 analog inputs. Each analog input can work either in voltage (0 - 10V) or power loop (0 - 20mA). TCW260 supports Modbus RTU interface for teracom and third-party sensors. RS-485 interface is fully insulated from the power supply.
Technical data:
Up to 24 channels for voltage (Volt) / Power (MA) or Energy Monitoring
Up to 24 Categorized Alarms with Flexible Setup parameters
4 Isolated digital inputs with S0 interface (EN62053-31)
On / Off and Counter (Counter) Digital Inputs
6 Isolated Analog Inputs with 0 - 20ma or 0 -10V. Br> RS-485 isolated interface with up to 24 Modbus RTU registers (sensors)
Password Protected Web based configuration and control