6 x digital inputs - Wet (active at DC input)
6 x Power relay outputs - 24VDC / 250VAC / 5A (COM, NO)
protocol: Modbus TCP / UDP
1 x RJ45 Ethernet Interface
I / O Pair Function - Input Mirrors for the second exit
digital inputs with counter - max 500Hz
Minimum pulse width: 1ms
Screw terminals: 10 - 30vdc / 3Watt
Forsyning | 10 - 30 VDC, 2,5 W via klemrække |
---|---|
Indgang | 6 stk. digitale Logisk 0: 0 - 4 VDC, Logisk 1: 10 - 50 VDC |
Netværk | 10/100 Mbit m/RJ45-stik |
Protokol | Modbus/TCP, TCP/IP og UDP |
Tæller | Indgange kan virke som 32 bit tæller, maks. frekvens 500 Hz |
Udgange | 6 stk. relæudgange: AC: 250 V og 5 A eller DC: 30 V og 5 A. Skiftetider Lukke/åben er 7ms / 3 ms |
ETHIO6I6PR-I provides six digital channels to contact and wet contact 6 electromechanical relays from form A. It has optical isolation to 3000 VDC of the transient over-voltage protection and has no channel-to-channel isolation. Each input channel can be used as a 32-bit counter. Ignition value and ensure value for the relay is programmable.
Note: When connected inductive loads to the relays, there may be a large electromotive force when the relay is activated because of the energy stored in the load . These flyback voltages can damage the relay contacts and shorten the lifetime of the relay sharply. Limit these flyback voltages at your inductive load by installing a flyback diode for DC loads or metal oxide varistor to vekselstrømsbelastninger.